Fault Isolation
4-4
First Edition
96047 
  
UPS is Not Communicating 
The following screen shows what happens if the UPS is not communicating. 
The above status might be caused by: 
Disconnected cables 
The AP9606 card is not configured properly. 
Check the status lights on the card. 
Link RX/TX LEDs 
Off 
The device which connects the Management Card to the 
network is turned off or it is not operating correctly.
Flashing 
The card is receiving data packets from the network.
Status LED 
Indicates the status of the Management Card
Off
The Management Card has no power.
Solid Green
The Management Card has valid network settings.
Flashing Green
The Management Card does not have valid TCP/IP 
settings. 
Solid Red
A hardware failure has been detected in the 
Management Card.
Contact StorageTek’s Customer Support Services.
Flashing Red
The Management Card is making BOOTP requests. If 
you do not use a BOOTP server, you need to configure 
the Management Card’s TCP/IP settings.