2–Pump 12-Station Controllers 
Chapter 3:  Installation 
29 
 BLOWBACK SETTINGS?
       NO/YES 
 
 SELECT PUMP 1 OR 2
USE KEYPAD TO ENTER 
 
  ENABLE BLOWBACK?
       NO/YES 
 
Changing Blowback Settings, Pump Settings Menu 
As an option, you can equip the conveying system filter chamber with a blowback feature to 
pulsate compressed air through the filter. This function cleans the filter after a pre-set number 
of load sequences. 
To set up the controller blowback feature, enter the Pump Settings menu, then: 
•  Press the MENU key until the Blowback Settings prompt screen displays: 
 
 
 
 
 
 
•  Press the YES key to alter the blowback settings. 
The following screen displays. 
 
 
 
 
 
 
 
 
 
Each pump can have separate blowback settings. To alter pump settings, select a pump: 
•  Using the keypad, enter the pump number (1 or 2). 
The following screen displays. 
 
 
 
 
 
 
 
 
 
To disable the blowback feature: 
•  Press the NO key. 
The screen returns to the Pump Settings menu. 
If you want to enable the blowback feature: 
•  Press the YES key.