To set the Username field (SNMP version 3 only):
  config set config.system.snmp.username2=yourusername .. 
  (replacing yourusername with the username config.system.snmp. 
  username2 (3 only)) 
To set the Engine ID field (SNMP version 3 only):
  config set config.system.snmp.password2=yourpassword .. 
  (replacing yourpassword with the password)
Once the fields are set, apply the configuration with the following com-
mand: 
  config run snmp
 
You can add a third or more SNMP servers by incrementing the “2” in 
the above commands, e.g. config.system.snmp.protocol3, config.system.
snmp.address3, etc. 
nfig instead of /etc/ssh_config 
/etc/config/users/<username>/.ssh/ instead of / 
      home/<username>/.ssh/  
Power Strip Control 
The console server supports a growing list of remote power-control 
devices (RPCs) which can be configured using the Management Console 
as described in Chapter 8. These RPCs are controlled using the open 
source PowerMan tools and with the pmpower utility.
PowerMan
PowerMan provides power management in a data center or compute 
cluster environment. It performs operations such as power on, power 
off, and power cycle via remote power controller (RPC) devices. Target 
hostnames are mapped to plugs on RPC devices in powerman.conf