Siemens G85139 Manuel D’Utilisation

Page de 42
English
5.  SYSTEM PARAMETERS
Parameter
Function
Range
[Default]
Description / Notes
G85139-H1750-U049-B
© Siemens plc 1997
26/09/97
30
P092  
Serial link baud rate
3  - 7
[6]
Sets the baud rate of the RS485 serial interface (USS protocol):
 = 1200 baud
4 = 2400 baud
5 = 4800 baud
 = 9600 baud
7 = 19200 baud
Note:
Some RS232 to RS485 converters are not capable of
baud rates higher than 4800.
P093  
Serial link timeout (seconds)
0 - 240
[0]
This is the maximum permissible period between two incoming data
telegrams. This feature is used to turn off the inverter in the event of a
communications failure.
Timing starts after a valid data telegram has been received and if a
further data telegram is not received within the specified time period,
the inverter will trip and display fault code F008.
Setting the value to zero switches off the control.
P094  
Serial link nominal system setpoint
(Hz)
0 - 400.00
[50.00]
Setpoints are transmitted to the inverter via the serial link as
percentages. The value entered in this parameter represents 100%
(HSW = 4000H).
P095  
USS compatibility
0 - 2
[0]
0 = Compatible with 0.1 Hz resolution
1 = Enable 0.01 Hz resolution
2 = HSW is not scaled but represents the actual frequency value to
a resolution of 0.01 Hz (e.g. 5000 = 50 Hz).
P099  
Option module type
0 - 1
[0]
0 = Option module not present
1 = PROFIBUS module (enables parameters relating to PROFIBUS)
P101  
Operation for Europe or USA
0 - 1
[0]
This sets the inverter for European or USA supply and motor
frequency:
0 = Europe (50 Hz)
1 = USA (60 Hz)
Note:
After setting P101 = 1 the inverter  must be re-set to factory
defaults. i.e. P944 = 1 to automatically set P013 = 60 Hz,
P081 = 60 Hz, P082 = 1680 rpm and P085 will be displayed
in hp.
P111
Inverter power rating (kW/hp)
0.0 - 50.00
[
žžž]
Read-only parameter that indicates the power rating of the inverter in
kW. e.g. 0.55 = 550 W
Note:
If P101 = 1 then the rating is displayed in hp.
P112
Inverter type (model)
1 - 7
[
žžž]
Read-only parameter.
1 = MICROMASTER series 2 (MM2)
2 = COMBIMASTER
3 = MIDIMASTER
4 = MICROMASTER Junior (MMJ)
5 = MICROMASTER series 3 (MM3)
6 = MICROMASTER Vector (MMV)
7 = MIDIMASTER Vector (MDV)
P113
Inverter type (power rating)
0 - 29
[
žžž]
Read-only parameter.
0 = MM12
1 = MM25
2 = MM37
3 = MM55
4 = MM75
5 = MM110
6 = MM150
7 = MM220
= MM300
10 = MM12/2
11 = MM25/2
12 = MM37/2
13 = MM55/2
14 = MM75/2
15 = MM110/2
16 = MM150/2
17 = MM220/2
18 = MM300/2
19 = MM400/2
20 = MM37/3
21 = MM55/3
22 = MM75/3
23 = MM110/3
24 = MM150/3
25 = MM220/3
26 = MM300/3
27 = MM400/3
28 = MM550/3
29 = MM750/3