Schneider Electric Weather Radio ION8800 Manuel D’Utilisation
14
© 2007 Schneider Electric. All rights reserved.
Environmental Specifications (IEC62052-11)
Installation
D
ANGER
Do not power up the meter until the ground terminal is connected -- risk of
electric shock.
1.
Connect the ground terminal on the rear of the meter to a good earth
ground on the rack, using a 3.3 mm
ground on the rack, using a 3.3 mm
2
(12 AWG) wire. Ensure that the
terminal nut is tightened down securely onto the ground wire. The wire
must be a minimum of 30 cm long (11.8”) to allow racking and
unracking.
must be a minimum of 30 cm long (11.8”) to allow racking and
unracking.
2.
Slide the meter into the DIN standard 43862 rack (half-width 19 inch/
482.6 mm rack with plug-in Essailec connector).
482.6 mm rack with plug-in Essailec connector).
3.
Ensure the rear connector fits tightly.
4.
Tighten the 2 slot-head screws (M3 thread) into the front of the meter rack,
to hold the meter firmly in place.
to hold the meter firmly in place.
Mounting Location
Indoor use
Metrological
-10 to +45ºC (14 to +113ºF)
Operating Range
-25 to +55ºC (-13 to +131ºF)
No formation of ice
No formation of ice
Max. Altitude
2000 metres (6562 feet) above sea level
Display Operating Range -10 to +60ºC (14 to +140ºF)
Storage Range
Storage Range
-25 to +70ºC (-13 to +158ºF)
Relative Humidity Range
5 to 95% non-condensing
Enclosure Rating
IP51 (IEC60529)
Meter Ground
Terminal
465 mm (18.31”)
451 mm (17.76”)
133 mm (5
.24”
)
57.
1 m
m
(2.
25”)
37.9 mm (1.49”
)
7 mm
(0.28”)
M6
Cut-out for 482.6 mm (19”)
Chassis
482.6 mm (19”)
Rack
ION8800
Meter
Slot-head
Screws
Meter Essailec
Connector
Rack Essailec
Connector