  MACH®  Series
 
Gas-Fired Boiler 
Operation 
 
 
Page  29 
4.2.3  Emergency Shut-Off 
 
 
 
 
 
 
 
 
 
The main gas cock should be closed immediately if an 
emergency situation occurs.  
 
 
 
 
 
 
 
 
4.3
  
T
YPICAL 
B
OILER 
O
PERATING 
C
ONDITIONS
 
 
Natural Gas  
*(1030 Btu/cu. ft.) 
LP Gas 
**(2500 Btu/cu. ft.) 
Model 
Number 
  
  
Input 
Rating 
(Btu/hr) 
  
Gas 
Rate 
(CFH) 
Output 
Capacity 
(Btu/hr) 
Gas 
Rate 
(CFH) 
Output 
Capacity 
(Btu/hr) 
Total 
Amperage 
  
300 
300,000 
291* 
275,000 
120** 
275,000 
8 amps or less 
450 
450,000 
437* 
414,000 
180** 
414,000 
8 amps or less 
750
 
750,000 728*  712,500 
300* 
712,500 
8 amps or less
 
900 
900,000 
873* 
846,000 
360** 
846,000 
8 amps or less 
1050 
1,050,000 
1019* 
987,000 
420** 
987,000 
8 amps or less 
 
 
Note:  The heat exchanger is constructed and stamped for 50 psig maximum operating pressure and/or 200º F 
maximum temperature.   
 
Main Gas Cock 
WARNING!  
If overheating occurs or the gas supply 
fails to shut off, do not turn off or 
disconnect the electrical supply to the 
pump.  Instead, shut off the gas supply at a 
location external to the boiler. 
Emergency Shut-Off