Setting the I/O bus addresses
BAS-APG001-EN
93
Setting the I/O bus addresses
Each EX2 on the link with the Tracer MP581 must have a unique 
address. Configure the address using the DIP switches on the EX2 circuit 
board (Figure 50). Table 23 shows the DIP switch settings for expansion 
modules 1 through 4.
Figure 50.  DIP switch on board
Input/output terminal wiring
All input/output terminal wiring for the EX2 module must meet the fol-
lowing requirements:
All wiring must be in accordance with the National Electrical Code 
and local codes.
Use only 18 AWG twisted-pair wire with stranded, tinned-copper 
conductors.
Binary output wiring must not exceed 20 ft (6.1 m) and must be in 
conduit.
Binary input wiring must not exceed 20 ft (6.1 m) and must be in 
conduit.
Analog and 24 Vdc output wiring distances depend on the specifica-
tions of the receiving unit. Use shielding for analog and 24 Vdc 
outputs.
Do not run input/output wires in the same wire bundle with ac-power 
wires.
Table 23.  EX2 DIP switch settings
EX2 module
D1
D2
1
Off
Off
2
Off
On
3
On
Off
4
On
On