Trane TRACER SUMMIT BAS-APG001-EN Manuel D’Utilisation

Page de 156
Subsequent alarms
BAS-APG001-EN
101
Subsequent alarms
(UL 864: 49.8)
When multiple input signals are received from more than one smoke zone 
to initiate different automatic smoke-control sequence(s), the smoke-
control system shall continue automatic operation in the mode 
determined by the first signal received.
Once a floor-based smoke alarm is activated, the system will react as if 
that is the only alarm and will ignore all subsequent alarms, The supply, 
return and stair shaft smoke alarms are still allowed to affect the supply, 
return and stair shaft supply fans. Any reaction can be overridden at the 
smoke control panel.
To ignore all subsequent floor alarms, the program fragment in Figure 53 
on page 102
 has been tested and works correctly. Once an alarm is 
triggered by any floor-based smoke alarm, it will be the only smoke alarm 
reaction allowed. When the first alarm is received, it triggers two events; 
it writes the floor of the smoke alarm to analog variable 1 and sets a 
binary variable to hold the output at that value. That binary variable is 
held until all alarms are cleared by the fire smoke control system.
Table 28.  Operational priority
Current state of system
Manual 
override
Automatic 
smoke alarm
System self-test
Panel lamp test
HVAC 
(nondedicated)
Next 
stat
e of syst
em
Manual override
N/A
Actuator is 
overridden.
System self-test 
ends.
Panel lamp test 
can continue.
Actuator is 
overridden.
Automatic 
smoke alarm
Affects all non-
overridden 
actuators.
N/A
System self-test 
ends.
Panel lamp test 
ends.
HVAC system 
operation is 
completely 
suspended. 
Only smoke 
purge operation 
is allowed.
System self-test
System self-test 
is not allowed 
to start.
System self-test 
is not allowed 
to start.
N/A
Allowed. No 
change.
System self-test 
not used.
Panel lamp test
Panel lamp test 
is allowed to 
start.
Panel lamp test 
is not allowed 
to start.
Panel lamp test 
is allowed to 
start.
N/A
Panel lamp test 
is allowed to 
start.
HVAC 
(nondedicated)
HVAC system 
running, but 
overridden 
actuator will be 
affected.
HVAC opera-
tion is not 
allowed to start.
System self-test 
not used.
HVAC opera-
tion continues.
N/A