Chapter 8 Network variable bindings
122
BAS-APG001-EN
Tracer MP580/581 bindings
This section discusses which network variables will be necessary to 
achieve UUKL time performance requirements.   Only “generic” network 
variables, which are neither Space Comfort Controller (SCC) or Discharge 
Air Controller (DAC), are necessary.   Use of generic variables does not 
affect either BCU auto-bound network variables or SCC or DAC based 
network variables.
Receiving data
A network variable input (nvi) receives data from other devices on the 
LonTalk network. The generic network variable inputs, nviSwitch and 
nviPercent, that are commonly used in Tracer MP580/581 bindings are 
shown in Table 29
Sending data
A network variable output (nvo) sends data to other devices on the Lon-
Talk network. The generic network variable outputs, nvoSwitch and nvo-
Percent, that are commonly used in Tracer MP580/581 bindings are 
shown in Table 30
Heartbeated network variables
All necessary information can be sent using nvoSwitch (SNVT_switch) 
and nvoPercent (SNVT_lev_percent), which are “heartbeated” variables. 
All necessary information can be received using nviSwitch 
(SNVT_switch) and nviPercent (SNVT_lev_percent). Heartbeated 
variables are a means of indicating freshness of information and/or 
quality of the communication link. For more information regarding 
heartbeating, see “Understanding bindings” on page 130.
Table 29.  Tracer MP580/581 generic network variable inputs 
Variable name
SNVT
Data type
Description
nviSwitch01 … 
nviSwitch40
SNVT_switch
Binary
Bind to these 40 network variable inputs to communi-
cate binary values to the device.
nviPercent01 … 
nviPercent20
SNVT_lev_percent
Analog
Bind to these 20 network variable inputs to communi-
cate levels in percent to the device. The valid range is 
from –163.84% to 163.83% with a resolution of 0.005%.
Table 30.  Tracer MP580/581 generic network variable outputs 
Variable name
SNVT
Data type
Description
nvoSwitch01 … 
nvoSwitch40
SNVT_switch
Binary
These 40 network variable outputs communicate binary 
values to other devices.
nvoPercent01 … 
nvoPercent20
SNVT_lev_percent
Analog
These 20 network variable outputs communicate levels 
in percent to other devices. The valid range is from –
163.84% to 163.83% with a resolution of 0.005%.