Trane TRACER SUMMIT BAS-APG001-EN Manuel D’Utilisation

Page de 156
Applications of smoke control methods
BAS-APG001-EN
5
A disadvantage of the airflow method is that it supplies increased oxygen 
to a fire. Within buildings, the airflow method must be used with great 
caution. The airflow required to control a wastebasket fire has sufficient 
oxygen to support a fire 70 times larger than the wastebasket fire. The 
airflow method is best applied after fire suppression or in buildings with 
restricted fuel. For more information on airflow, oxygen, and combustion, 
refer to Huggett, C. 1980, Estimation of Rate of Heat Release by Means of 
Oxygen Consumption Measurements, Fire and Materials
.
Buoyancy method
The buoyancy method clears smoke from large volume spaces with high 
ceilings. The method employs paths to the outside and relies on hot 
combustion gases rising to the highest level in a space. At the high point, 
either a powered smoke exhausting system or a non-powered smoke 
venting system clears the smoke.
Applications of smoke control methods
Applying the methods of smoke control to spaces within a building 
provides a building smoke control system. Smoke control methods are 
most commonly applied to building spaces to provide zoned, stairwell, 
elevator shaft, and atrium smoke control.
Zoned smoke control
Zoned smoke control uses compartmentation and pressurization to limit 
smoke movement within a building. Typically, a building consists of a 
number of smoke control zones. Barriers (partitions, doors, ceilings, and 
floors) separate the zones. Each floor of a building is usually a separate 
zone (Figure 3 on page 6). However, a zone can consist of more than one 
floor, or a floor can consist of more than one zone.
The zone in which the smoke is detected is the smoke control zone. Zones 
next to the smoke control zone are adjacent zones. Zones not next to the 
smoke control zone are unaffected zones.
Pressure differences produced by fans limit smoke movement to adjacent 
and unaffected zones. The system may pressurize adjacent zones and 
leave all unaffected zones in normal operation (Figure 3(a) and Figure 
3(c), page 6). Pressurizing adjacent zones creates a pressure sandwich. 
Or, the system may pressurize adjacent zones and some unaffected zones 
(Figure 3(b), page 6). In either case, the system exhausts the smoke 
control zone, putting it at a negative pressure, relative to adjacent zones.
Note:
It is beyond the scope of this user guide to provide 
mathematical design analysis information for smoke control. 
For references to design analysis information, see Appendix A, 
References.