Chapter 2 Pre-installation considerations
26
BAS-APG001-EN
and dampers: status switches, differential pressure switches, airflow 
paddle switches, current-sensing relays, limit switches, and end switches.
Status switches at fans and dampers monitor the operation of the devices. 
Multiple binary inputs at the Tracer MP581s verify the On and Off status 
of fans and the Open and Closed status of dampers. If a status switch 
does not confirm the commanded (automatic or manual) operation, a Fail 
indicator activates at the FSCS. Failure detection must incorporate a 
time delay to give the devices time to function.
Differential pressure switches, airflow paddle switches, and current-
sensing relays monitor fan operations. Differential switches piped across 
fan and paddle switches in the air stream can give erroneous indications.
IMPORTANT
A current-sensing relay is the preferred way to confirm the operating 
status of a fan.
Limit switches and end switches monitor dampers. The switches activate 
damper Open and Closed signals for the FSCS. The damper blades 
activate the switches. Some codes require two switches in order to sense 
both the fully opened and fully closed position of the damper.
Tracer MP581 programmable controller
The Tracer MP581 must have multiple binary inputs to verify the On and 
Off operation of fans. It must also have multiple binary inputs to verify 
the Open and Closed positions of dampers.
Equipment supervision
Equipment supervision is a pre-installation consideration. Smoke control 
equipment must be supervised to ensure it is operational. Supervision 
techniques consist of confirming communications among system control 
panels, confirming operation in normal use situations, and performing 
weekly self-tests.
Confirming communications among all system control panels is a 
supervision technique that monitors basic system integrity. If any panel 
loses its communications, a Trouble alert is sent to the FSCS.
Normal use operations confirm the integrity of field point wiring for 
nondedicated equipment. Nondedicated equipment provides conditioned 
air to the building daily. When nondedicated equipment is not 
operational, comfort conditions deteriorate and building tenants notify 
maintenance personnel.