Trane TRACER SUMMIT BAS-APG001-EN Manuel D’Utilisation

Page de 156
Chapter 4 Installing the Tracer Summit BMTX BCU
48
BAS-APG001-EN
Connecting the main circuit board
The main circuit board is attached to a plastic frame. It is shipped 
separately. The board can be kept in the office and programmed while the 
back of the enclosure is mounted and the termination board, which is 
attached to the back of the enclosure, is wired. After programming has 
been completed, connect the circuit board to the termination board as 
shown in the following procedure.
To connect the circuit board:
1.
Verify that the 24 Vac power cable is not connected to the termination 
board.
2.
Hold the circuit board frame at a 90° angle to the back of the 
enclosure, as shown in Figure 21.
3.
Connect the circuit board’s 60-pin ribbon cable to the termination 
board’s 60-pin slot. The connector is keyed to the slot. To avoid 
difficulty, make sure that the key is lined up with the slot.
Figure 21.  Connecting the circuit board ribbon cable
1.
Align the snaps on the circuit board frame with the mounting locks at 
opposite ends of the enclosure back, as shown in Figure 22 on page 49.
2.
Using the tabs that are at both ends of the top frame, push the two 
frames together. You will hear a click when the frames connect.