Trane TRACER SUMMIT BAS-APG001-EN Manuel D’Utilisation

Page de 156
BAS-APG001-EN
53
Chapter 5
Installing the Tracer MP581 
programmable controller
Installation guidelines
Guidelines for installing a Tracer MP581 include:
A Tracer MP581 that monitors the fire alarm control panel for 
consistency (FACP) must be installed in the same room as the FACP. 
It must be installed within 20 feet of the FACP. Cables between the 
FACP and the Tracer MP581 must be in conduit.
A Tracer MP581 that monitors and controls the fire smoke control 
system (FSCS) must be installed in the same room as the FSCS. It 
must be installed within 20 feet of the FSCS. Cables between the 
FACP and Tracer MP581 must be in conduit.
IMPORTANT
Wiring between the Tracer MP581 and the FACP and between the Tracer 
MP581 and the FSCS (point wiring) must be in conduit. The conduit 
requirement is necessary, since the binary inputs to the Tracer MP581 
are not supervised.
Wiring from a Tracer MP581 to field sensors and relays is not 
supervised. Installation of this wiring must conform to more stringent 
requirements when a Tracer MP581 is part of a smoke control system 
than when it is part of a standard mechanical system control.