Chapter 5 Installing the Tracer MP581 programmable controller
80
BAS-APG001-EN
Binary output LEDs
The BO1–BO6 LEDs indicate the status of the six binary outputs. 
Table 18 describes binary output LED activity.
Service LED
The red Service LED indicates whether the controller is operating nor-
mally. Table 19 describes Service LED activity. 
Note:
Each binary output LED reflects the status of the output relay on the 
circuit board. It may or may not reflect the status of the equipment 
the binary output is controlling. Field wiring determines whether the 
state of the binary output LED also applies to the status of the end 
device. Table 18 describes the LED states.
Table 18.  Binary output LEDs
LED activity
Explanation
LED is on continuously
The relay output is energized.
LED is off continuously
The relay output is de-energized or there is no 
power to the board.
Table 19.  Red Service LED
LED activity
Explanation
LED is off continuously 
when power is applied to 
the controller
The controller is operating normally.
LED is on continuously 
when power is applied to 
the controller
The controller is not working properly, or 
someone is pressing the Service Pin button.
LED flashes once every 
second
The controller is not executing the application 
software because the network connections 
and addressing have been removed.
1
1
Restore the controller to normal operation using the Rover service tool. Refer to 
 
EMTX-SVX01D-EN for more information.