Trane OA1D OA2D OA3D (Indirect Gas-Fired/Electric Heat) Manuel De Maintenance

Page de 56
Installation
28
 OAU-SVX01E-EN
Note: All field installed wiring must conform to NEC 
guidelines as well as State and Local codes.
Verify that the power supply available is compatible with 
the unit’s nameplate ratings. The available supply power 
must be within 10  percent of the rated voltage stamped on 
the nameplate. Use only copper conductors to connect the 
power supply to the unit.
Main Unit Power
Standard Wiring
The electrical service must be protected from over current 
and short circuit conditions in accordance with NEC 
requirements. Protection devices must be sized according 
to the electrical data on the nameplate.
1.
Location of the applicable electrical service entrance is 
illustrated in 
. Complete the unit’s power wiring 
connections onto either; the main terminal block HTB1 
inside the unit control panel, the factory mounted non-
fused disconnect switch (UCD) or circuit breaker (UCB), 
or the electric heat non-fused disconnect switch. Refer 
to the customer connection diagram that shipped with 
the unit for specific termination points.
2. Provide proper grounding for the unit in accordance 
with local and national codes.
Use the following checklist in conjunction with the 
checklist in 
 to ensure 
that the unit is properly installed and ready for operation.
Voltage Imbalance
Three phase electrical power to the unit must meet 
stringent requirements for the unit to operate properly. 
Measure each leg (phase-to-phase) of the power supply. 
Each reading must fall within the utilization range stamped 
on the unit nameplate. If any of the readings do not fall 
Table 6.
OA3D Unit
MBh
Pipe Connection (in.)
300
3/4
350
1
400
1
500
1
600
1-1/4
700
1-1/4
800
1-1/4
1000
1-1/4
WARNING
Hazardous Voltage!
Disconnect all electric power, including remote 
disconnects before servicing. Follow proper lockout/
tagout procedures to ensure the power can not be 
inadvertently energized. Failure to disconnect power 
before servicing could result in death or serious injury.
NOTICE: 
Use Copper Conductors Only!
Unit terminals are not designed to accept other types 
of conductors. Failure to use copper conductors could 
result in equipment damage.
WARNING
Proper Field Wiring and Grounding 
Required!
All field wiring MUST be performed by qualified 
personnel. Improperly installed and grounded field 
wiring poses FIRE and ELECTROCUTION hazards. To 
avoid these hazards, you MUST follow requirements for 
field wiring installation and grounding as described in 
NEC and your local/state electrical codes. Failure to 
follow code could result in death or serious injury.
Verify that the correct size and number of filters are in 
place.
Inspect the interior of the unit for tools and debris and 
install all panels in preparation for starting the unit.
Check all electrical connections for tightness and 
“point of termination” accuracy.
Verify condenser airflow is unobstructed.
Verify that the condenser and indoor fans turn freely 
without rubbing and are properly tightened on the 
shafts.
Check motor mounting bolts and inlet cone for 
tightness. Free spin wheel by hand to check for proper 
alignment of motor, wheel, and inlet cone. Record 
motor nameplate amps at unit-rated voltage.
Check proper indoor fan wheel rotation. Wheel 
housing will be marked to indicate direction of proper 
rotation.
With access doors closed and secured, operate 
blower at 100 percent speed. Check amp readout of 
amps output to indoor fan at VFD display to confirm 
operation within motor amp capacity.
WARNING
Live Electrical Components!
During installation, testing, servicing and 
troubleshooting of this product, it may be necessary to 
work with live electrical components. Have a qualified 
licensed electrician or other individual who has been 
properly trained in handling live electrical components 
perform these tasks. Failure to follow all electrical 
safety precautions when exposed to live electrical 
components could result in death or serious injury.