OPERATION 
 
 
 
 
MOVING THE CIRCUIT BREAKER FROM 
THE CONNECTED TO THE DISCONNECTED 
POSITION 
 
Hazard of fire, explosion, 
severe injury, death and 
property damage.  Circuit 
breaker must be OFF 
before moving to or from 
the CONNECTED position. 
 
TO MOVE THE CIRCUIT BREAKER TO THE 
DISCONNECTED POSITION: 
 
1.  Check to be sure that the On-Off Indicator 
reads OFF (Green).  Push the manual trip 
lever in the direction of the arrow if 
necessary to open the circuit breaker.  The 
interlock release lever cannot be raised 
unless the circuit breaker is OFF. 
 
2.  Grasp the handles on the breaker with both 
hands and, while lifting the interlock 
release lever with the left hand, pull the 
breaker out of the cell until the arrow on the 
front cover indicates the DISCONNECTED 
position has been reached (Fig. 23), then 
release the lever.  Check to make sure the 
interlock release lever has returned to its 
original lowered position. 
 
3.  Optionally, disconnect the control circuit plug 
from the breaker (Fig. 24).  The plug may 
remain connected if desired in order to 
perform tests on the control circuit with main 
power removed from the circuit breaker.  If 
the plug is disconnected, it must be 
reconnected before the circuit breaker is 
returned to the CONNECTED position. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Fig. 23  Breaker at DISCONNECTED Position 
 
 
 
 
 
 
Fig. 24  Disconnect Control Circuit Plug 
    
DANGER
 