Toshiba VF010H05 Manuel D’Utilisation
JKSSS+ Series - 66
JKSSS+ Series
2.3 - 4.2KV
SP.11 Communications (Setpoint Page 11)
(Security Level: 3)
(Security Level: 3)
SP11.1 Set Front Baud Rate: Configures the RS232
communications baud rate.
SP11.2 Set Modbus Baud Rate: Configures the
Modbus communications baud rate.
SP11.3 Modbus Address Number: Assigns a Modbus
address to the soft starter relay.
SP11.4 Set Access Code: Assigns an access code to
the Modbus addressing. This is typically not
used.
used.
SP11.5 Set Link Baud Rate: Configures the RS422
communications baud rate between the keypad
operator and the CPU board. (For applications
with remote keypad only.)
operator and the CPU board. (For applications
with remote keypad only.)
SP11.6 Remote Start/Stop: Allows the RS485 Modbus
communications to start and stop the motor.
Contact factory for details.
Contact factory for details.
MENU
PAGE 11
COMMUNICATIONS
SET FRONT BAUD
RATE: 9.6 KB/SEC
(Hit DOWN ARROW ten times)
Range: 2.4, 4.8, 9.6, 19.2
38.4 KB/SEC
SET MODBUS BAUD
RATE: 9.6 KB/SEC
MODBUS ADDRESS
NUMBER: 247
SET ACCESS CODE
CODE: 1
Range: 2.4, 4.8, 9.6, 19.2
38.4 KB/SEC
Range: 1 - 247
Increments of 1
Range: 1 - 999
Increments of 1
SET LINK BAUD
RATE: 38.4 KB/SEC
Range: 2.4, 4.8, 9.6, 19.2
38.4 KB/SEC
REMOTE START/STOP:
DISABLED
Option: Enabled or Disabled