Toshiba 18 - 1250 A Manuel D’Utilisation

Page de 99
TE Series        
          Digital Solid State Soft Starters   18 – 1250A 
88 
Appendix 6 (cont.) Soft Starter Settings Record
 
 
 
 
 
 
 
 
Fn #  Group 
Function Description 
Adjustment / Display Range 
Setting 
Increments
Factory 
Setting 
Setting 
Setting 
F024 
Pump Flex Dec
e
Mode
 
Pump Flex Control  / 
Deceleration Ramp  
0 = Disabled (coast to stop)  
1 = Enabled, except after OL trip 
2 = Enabled, continued Decel even 
if there is an OL trip 
Disabled 
 
 
F025 
Begin Decel Level (BDL), 
Immediate Drop Down Torque 
0 - 100 % of Output Voltage 
1% 
60% 
 
 
F026 
Decel Shut Off Voltage 
0 to (BDL minus 1)% Voltage 
1% 
30% 
 
 
F027 
Decel Ramp Time 
1 – 60 Seconds 
1 second 
10 
seconds 
 
 
F028 
Restart
 
Restart Delay Time  
(Sequential Start Delay) 
0 = Disabled, or 
1-999 seconds after a Power Loss 
(Status can be read in F054) 
1 second 
Disabled 
 
 
F029 
Reserved for Factory Use 
 
 
 
 
 
F030 
Run Timer 
a
nd Time Clock Co
n
troller 
Mo
des
 
Process Control Timer 
Selection 
0 = Disabled (No timer operation) 
1 = Minimum Batch Run Timer 
2 = Permissive Run Timer 
Disabled 
 
 
F031 
Run Timer Time  
for use in F030 above 
1-9999 minutes after a Start 
Command or Start Event from TCC 
1 1 
 
 
F032 
24hr 
Time Clock Controller (TCC)  
Start Event Mode.  
 
Chose from “One Shot”  
or 1 to 7 “Start Events”  
in  F033 – F039 
 
Run time for this mode comes 
from F030 above. 
 
Start Event Cycle (SEC) Settings 
0 = One Shot: Start Event comes 
from Start command only 
1 = Loop SEC every day 
2 = Loop SEC every 2
nd
 day 
3 = Loop SEC every 3
rd
 day 
4 = Loop SEC. every 4
th
 day 
5 = Loop SEC. every 5
th
 day 
6 = Loop SEC. every 6
th
 day 
7 = Loop SEC one day per week 
8 = Single 24hr SEC  
(until programmed again) 
One Shot 
 
 
F033 
Start Event #1 Start Time 
00:00-23:59 (hh:mm) or OFF 
OFF 
 
 
F034 
Start Event #2 Start Time 
00:00-23:59 (hh:mm) or OFF 
OFF 
 
 
F035 
Start Event #3 Start Time 
00:00-23:59 (hh:mm) or OFF 
OFF 
 
 
F036 
Start Event #4 Start Time 
00:00-23:59 (hh:mm) or OFF 
OFF 
 
 
F037 
Start Event #5 Start Time 
00:00-23:59 (hh:mm) or OFF 
OFF 
 
 
F038 
Start Event #6 Start Time 
00:00-23:59 (hh:mm) or OFF 
OFF 
 
 
F039 
Start Event #7 Start Time 
00:00-23:59 (hh:mm) or OFF 
OFF