Extended parameters
• Input/output parameters 1
Title
Communication
No.
Function
Unit
Minimum
setting unit
Panel/Commun
ication
Adjustment range
Default
setting
User
setting
Reference
E6581158
H
0100
Low-speed signal
output frequency
Hz
0.1/0.01
0.0-HJ
0.0
6.1.1
H
0101
Speed reach
setting frequency
Hz
0.1/0.01
0.0-HJ
0.0
6.1.3
H
0102
Speed reach
detection band
Hz
0.1/0.01
0.0-HJ
2.5
6.1.2
H
0105
Priority selection
(Both F-CC and
R-CC are ON)
-
-
0: Reverse
1: Slowdown Stop
1
6.2.1
H
0108
Always active
function selection 1
-
-
0-65 (No function)
0
6.3.1
0: Analog input for communications
VIB 
- analog input
1: VIA - analog input
VIB 
- contact input (Sink)
2: VIA - analog input
VIB 
- contact input (Source)
3: VIA 
- contact input (Sink)
VIB 
- contact input (Sink)
H
0109
Analog/contact
input function
selection (VIA/VIB
terminal)
-
-
4: VIA 
- contact input (Source)
VIB 
- contact input (Source)
0
6.2.2
H
0110
Always-active
function selection 2
-
-
0-65 (ST)
1
6.3.1
H
0111
Input terminal
selection 1 (F)
-
-
0-65 (F)
2
H
0112
Input terminal
selection 2 (R)
-
-
0-65 (R)
3
H
0113
Input terminal
selection 3 (RES)
-
-
0-65 (RES)
10
H
0114
Input terminal
selection 4 (S1)
-
-
0-65 (SS1)
6
H
0115
Input terminal
selection 5 (S2)
-
-
0-65 (SS2)
7
H
0116
Input terminal
selection 6 (S3)
-
-
0-65 (SS3)
8
H
0117
Input terminal
selection 7 (VIB)
-
-
5-17 (SS4)
9
H
0118
Input terminal
selection 8 (VIA)
-
-
5-17 (AD2)
5
6.3.2
H
0130
Output terminal
selection 1A
(RY-RC)
-
-
0-255 (LOW)
4
H
0131
Output terminal
selection 2A
(OUT-NO)
-
-
0-255 (RCH)
6
H
0132
Output terminal
selection 3 (FL)
-
-
0-255 (FL)
10
6.3.3
H
0137
Output terminal
selection 1B
(RY-RC)
-
-
0-255 (always ON)
255
H
0138
Output terminal
selection 2B
(OUT-NO)
-
-
0-255 (always ON)
255
6.3.4