3. SIGNALS AND WIRING
3.5 Power line circuit
CAUTION
When the servo amplifier has become faulty, switch power off on the amplifier
power side. Continuous flow of a large current may cause a fire.
Switch power off at detection of an alarm. Otherwise, a regenerative brake
transistor fault or the like may overheat the regenerative brake resistor, causing a
fire.
POINT
For the power line circuit of the MR-J2S-11KB to MR-J2S-22KB, refer to
Section 3.12 where the power line circuit is shown together with the servo
motor connection diagram.
Section 3.12 where the power line circuit is shown together with the servo
motor connection diagram.
3.5.1 Connection example
Wire the power supply/main circuit as shown below so that power is shut off and the servo-on command
turned off as soon as an alarm occurs, a servo forced stop is made valid, or a controller emergency stop is
made valid. A no-fuse breaker (NFB) must be used with the input cables of the power supply.
turned off as soon as an alarm occurs, a servo forced stop is made valid, or a controller emergency stop is
made valid. A no-fuse breaker (NFB) must be used with the input cables of the power supply.
(1) For 3-phase 200 to 230VAC power supply
EM1
COM
OFF
ON
MC
MC
SK
NFB
MC
L
1
L
2
L
3
L
11
L
21
VDD
SG
(Note)
Alarm
RA1
Controller
emergency stop
RA2
Forced
stop
Servo amplifier
Forced stop
Power supply
3-phase
200 to 230VAC
3-phase
200 to 230VAC
Note: Configure up the power supply circuit which switches off the magnetic contactor after detection of
alarm occurrence on the controller side.