Taurus Group 60 Manuel D’Utilisation

Page de 83
Turbomachinery Package Specification 
Taurus
 60 Compressor Set and Mechanical Drive 
•  Pilot air operated secondary gas fuel shutoff valve 
•  Pilot air operated gas vent valve 
•  Electrically operated fuel control valve 
•  Torch with shutoff valve and pressure regulators 
•  Main fuel manifold 
•  Fuel injectors 
For SoLoNOx combustion, the fuel system also includes: 
•  Fuel pilot control valve 
•  Fuel pilot manifold 
•  Inlet gas filter/coalescer loose shipped for field installation 
Component Operation 
The gas fuel pressure supplied to the turbine skid must meet minimum and maximum 
pressure and flow requirements. If the gas fuel pressure is too high or too low, the control 
system will prevent turbine operation. Pneumatically actuated primary and secondary gas 
fuel shutoff valves are controlled using pilot air pressure. For each valve, pilot air 
pressure is admitted to and exhausted from a pneumatic actuator through a solenoid 
valve. Fail-safe operation ensures both valves will close in case pilot air pressure is lost. 
The gas fuel control valve and, when applicable, the SoLoNOx fuel pilot control valve, are 
powered by integrated DC motor-driven actuators. Integrated actuator electronics provide 
precise closed-loop valve control based on position command inputs versus position 
feedback outputs. Both valves are fast acting and provide fuel metering for light-off, 
acceleration, full load, and load transient conditions. Fail-safe operation ensures both 
valves will close in case the command signal or control power is lost. During the start 
sequence prior to ignition, the control system will verify gas pressure and perform a gas 
valve check to verify proper operation of all gas fuel valves. 
 
Table 8. 
Fuel System Specifications 
Gas Fuel System 
Acceptable Gas Fuels See Note (a) 
Natural Gas 
Propane 
Fuel Quality 
Refer to Solar’s Engineering Specification ES 9-98 
Optional Fuel System Types 
Conventional Combustion or SoLoNOx 
Combustion 
Compliance 
National Association of Corrosion Engineers 
(NACE) Compliant 
Minimum/Maximum Gas Fuel Supply Pressure 
1170 to 2068 kPag (170 to 300 psig), See Note (b) 
Minimum Flow Rate 
1475 kg/hr (3250 lb
m
/hr), See Note (b) 
Minimum/Maximum Fuel Supply Temperature 
-40° to 93°C (-40° to 200°F), See Note (c) 
Primary Gas Fuel Shutoff Valve 
Pneumatically Actuated Spring-Closed Ball Valve 
Secondary Gas Fuel Shutoff Valve 
Pneumatically Actuated Vane Type Valve 
Gas Fuel Control Valve and SoLoNOx Fuel Pilot 
Control Valve (If Applicable) 
Actuator Valve 
Actuator Voltage 
120 VDC 
Valve Discrete Signals 
24 VDC 
Valve Analog Signals 
4 to 20 mA 
Maximum Operating Pressure 
1380 kPag (200 psig) 
Maximum Operating Temperature 
93°C (200°F) 