D.  Calculating Alternate Floor Protection Material 
Thermal Conductivity: k value
The k value indicates the amount of heat (in BTU’s) that will fl ow 
in 1 hour throught 1 square foot of a uniform material 1 inch thick 
for each degree (F) of temperature difference from one side of 
the material to the other.  The LOWER the k factor means less 
heat is being conducted through the non-combustible material to 
the  combustible  material  beneath  it.   The  k  value  of  a  material 
must be equal or smaller then the required k value to be accept-
able.
 
(BTU) (inch)
 
 
(foot
2
 (hour) (
o
F)
Thermal Resistance: R value
The  R  value  is  a  measure  of  a  material’s  resisteance  to  heat 
transfer.  R value is convenient when more than one material is 
used since you can add the R values together, whereas you can 
not  do  this  for  k  value.   The  HIGHER  the  R  factor  means  less 
heat is being conducted through the non-combustible material to 
the combustible material beneath it.  The R value of a material 
must be equal or larger then the required R value to be accept-
able.
Converting k to R:
Divide 1 by k and multiply the results times th thickness in inches 
of the material.
 
R = 1/k x inches of thickness
Converting R to k:
Divide the inches of thickness by R.
 
k = inches of thickness/R
Calculatons:
Example: Floor protection requires k value of .84, 3/4 inch thick.
Alternative material has a k value of .6 and is 3/4 inch thick.
Divide .6 by .75 = k value of .80.  This k value is smaller than .84 
and therefore is acceptable.