page 18 — dca70ssJu4i 60 hz generator • operation and parts manual — rev. #2 (04/09/14) 
geNeRaTOR
This generator (Figure 4) is designed as a high quality 
portable (requires a trailer for transport) power source for 
telecom sites, lighting facilities, power tools, submersible 
pumps and other industrial and construction machinery.
operating panel
The “Operating Panel” is provided with the following:
 
„
ECU Controller
 
„
Gauge Unit Assembly
• Oil Pressure Gauge
• Water Temperature Gauge
• Charging Voltmeter
• Fuel Gauge
• Tachometer
 
„
Panel Light/Panel Light Switch
 
„
Hour Check Button
 
„
Auto Start/Stop Switch
 
„
Fuel Leak Detected Alarm Lamp
control panel
The “Control Panel” is provided with the following:
 
„
Frequency Meter (Hz)
 
„
AC Ammeter (Amps)
 
„
AC Voltmeter (Volts)
 
„
Ammeter Change-Over Switch
 
„
Voltmeter Change-Over Switch
 
„
Voltage Regulator
 
„
3-Pole, 200 amp Main Circuit Breaker
 
„
“Control Box” (located behind Control Panel)
• Automatic Voltage Regulator
• Current Transformer
• Over-Current Relay
• Starter Relay
output terminal panel
The “Output Terminal Panel” is provided with the following:
 
„
Three 120/240V output receptacles (CS-6369), 50A
 
„
Three auxiliary circuit breakers, 50A
 
„
Two 120V output receptacles (GFCI), 20A
 
„
Two GFCI circuit breakers, 20A
 
„
Eight output terminal lugs (3Ø power)
 
„
Ground lug
 
„
Battery Charger (Option)
 
„
Water Heating Element (Option)
 
„
Camlock Connector (Option)
 
„
600 VAC Output, Auto-Transformer (Option)
open delta excitation sYstem
Each generator is equipped with the state of the art 
“open-
delta” excitation system. The open delta system consist 
of an electrically independent winding wound among 
stationary windings of the AC output section.
There are four connections of the open delta A, B, C and 
D. During steady state loads, the power from the voltage 
regulator is supplied from the parallel connections of A to 
B, A to D, and C to D. These three phases of the voltage 
input to the voltage regulator are then rectified and are the 
excitation current for the exciter section. 
When a heavy load, such as a motor starting or a short 
circuit occurs, the automatic voltage regulator (AVR) 
switches the configuration of the open delta to the series 
connection of B to C. This has the effect of adding the 
voltages of each phase to provide higher excitation to the 
exciter section and thus better voltage response during the 
application of heavy loads. 
The connections of the AVR to the AC output windings are 
for sensing only. No power is required from these windings.
The open-delta design provides virtually unlimited excitation 
current, offering maximum motor starting capabilities. The 
excitation does not have a 
“fixed ceiling” and responds 
according the demands of the required load.
engine
This generator is powered by a 4 cylinder, 4-cycle water 
cooled, direct injection, turbocharged, air cooled and EGR 
John Deere
 4045HFG92
 
diesel engine. This engine is 
designed to meet every performance requirement for the 
generator. Reference Table 2 for engine specifications. 
In keeping with MQ Power’s policy of constantly improving 
its products, the specifications quoted herein are subject 
to change without prior notice.
electric governor sYstem
The electric governor system controls the RPMs of the engine.  
When the engine demand increases or decreases, the 
governor system regulates the frequency variation to ±.25%. 
extension caBles
When electric power is to be provided to various tools or 
loads at some distance from the generator, extension cords 
are normally used. Cables should be sized to allow for 
distance in length and amperage so that the voltage drop 
between the generator and point of use (load) is held  to 
a minimum. Use the cable selection chart (Table 8) as a 
guide for selecting proper extension cable size.
GeNeraL iNFOrMatiON