Lexicon 570 Manuel D’Utilisation
34
Dancer Communications, Inc.
COMMAND>INP R
INPUT STATUS REPORT
===== ====== ======
Input #1 OK -94 F
Input #2 OK -78 F
Input #3 OK -89 F
Input #4 OK -93 F
Input #5 OK -93 F
Input #6 OK -93 F
Input #7 OK -93 F
Input #8 OK -93 F
Time: 08/03/96 05:53:21
Input Operation Parameters
Type INP O at the command prompt to get a sub-menu parameters (applied globally to all inputs) that affect the
sensitivity and responsiveness of the monitored inputs.
sensitivity and responsiveness of the monitored inputs.
COMMAND>INP O
INPUT OPERATIONS
===== ==========
1 = Input Dampening: Enabled
2 = Input Deadband: 1
3 = Rate of change period: 00:00:10 (hh:mm:ss)
0 = Previous Menu
Input Damping
Input damping causes the Messenger 570 to react slowly to a rapidly changing input. For example, if
temperature were being monitored and the temperature probe was moved from an ice bath to a hot water
bath, a damped input would show a gradual change in temperature every 10 to 20 seconds, rather than an
instantaneous change. This option will eliminate many false alarm situations.
temperature were being monitored and the temperature probe was moved from an ice bath to a hot water
bath, a damped input would show a gradual change in temperature every 10 to 20 seconds, rather than an
instantaneous change. This option will eliminate many false alarm situations.
COMMAND>INP O
INPUT OPERATIONS
===== ==========
1 = Input Dampening: Enabled
2 = Input Deadband: 1
3 = Rate of change period: 00:00:10 (hh:mm:ss)
0 = Previous Menu
Choose a Number>1
Input Dampening is Enabled
Change Present State? [y/n]> No
Deadband
When set to a value greater than 1, the Messenger 570 system will not report a change in input value until
the change exceeds the deadband.
the change exceeds the deadband.