IPSO TMB1268C Manuel D’Utilisation

Page de 18
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Tumblers – 120 and 170
14
3-09-71
Manifold Venting
While it is preferable to exhaust tumblers individually 
to the outdoors, a main collector duct may be used if it 
illustration indicates minimum diameters, which 
should be increased if the collector length exceeds 14 
feet (4.3 meters) and two 90° elbows. The diameter of 
a round duct must be increased by 10% for each 
additional 20 feet (6.1 meters). Cross sectional area of 
a rectangular or square duct must be increased 20% for 
each additional 20 feet (6.1 meters). Refer to Table 3 
and Table 4 to determine equivalent ducting sizing. 
The collector duct may be rectangular or square in 
cross section, as long as the area is not reduced. 
Provisions MUST be made for lint removal and 
cleaning of the collector duct.
The vent collector system must be designed so the 
static back pressure measured 12 inches (305 mm) 
from the exhaust outlet does not exceed the maximum 
allowable pressure specified on the installation sticker 
on the rear of tumbler. Static back pressure must be 
measured with all tumblers vented into the collector 
operating.
NOTE: Never connect a tumbler duct at a 90° 
angle to the collector duct. Refer to Figure 3. Doin
so will cause excessive back pressure, resulting in 
poor performance. Never connect two tumbler 
exhaust ducts directly across from each other at the 
point of entry to the collector duct.
With the tumbler in operation, airflow at any point in 
the duct should be at least 1200 feet per minute (366 
meters per minute) to ensure that lint remains airborne. 
If 1200 feet per minute cannot be maintained, schedule 
monthly inspections and cleaning of the ductwork. 
Figure 3 
T438I