APC Fluid Cooler 57MBH@25 TD, 10GPM, 5Feeds, 400/3/50 ACFC75256 Manuel D’Utilisation

Codes de produits
ACFC75256
Page de 56
23
InRow RD Technical Data Manual
ACRD500 Series
% Fan Speed
Voltage
L/S (SCFM) Unit Power in kW
Condenser 
Fan Power in 
kW
Net Sensible 
Capacity kW 
(BTU/h)
SA Temp 
°
C (
°
F)
Return Air Temperature = 29.4° C (85° F)
30
All
700 (1400)
2.03
0.01
7.3 (24,931)
20.8 (69.5)
1
40
All
900 (1800)
3.25
0.02
9.8 (33.469)
20.8 (69.5)
1
50
All
1100 (2300)
4.28
0.03
12.1 (41,324)
20.8 (69.5)
1
60
All
1300 (2800)
6.32
0.06
14.5 (49,520)
20.8 (69.5)
70
All
1500 (3200)
7.12
0.07
16.9 (57.717)
20.8 (69.5)
80
All
1700 (3700)
9.13
0.10
19.4 (66,254)
20.8 (69.5)
90
All
2000 (4100)
9.52
0.18
21.8 (74,451)
20.8 (69.5)
100
All
2200 (4600)
11.74
0.31
24.2 (82,647)
20.8 (69.5)
Return Air Temperature = 35° C (95° F)
30
All
700 (1400)
4.28
0.05
11.95 (40,811)
20.8 (69.5)
1
40
All
900 (1800)
6.51
0.08
15.93 (54,404)
20.8 (69.5)
50
All
1100 (2300)
7.65
0.14
19.91 (67,996)
20.8 (69.5)
60
All
1300 (2800)
10.19
0.20
23.89 (81,589)
20.8 (69.5)
70
All
1500 (3200)
12.28
0.27
27.87 (95.181)
20.8 (69.5)
80
All
1700 (3700)
14.66
0.45
30.6 (104,505)
21.4 (70.5)
90
All
2000 (4100)
15.09
0.55
33.0 (112,701)
21.9 (71.5)
100
All
2200 (4600)
15.69
0.60
33.7 (115,092)
23 (73.4)
Return Air Temperature = 40.6° C (105° F)
30
All
700 (1400)
7.13
0.09
16.6 (56,692)
20.8 (69.5)
1
40
All
900 (1800)
9.46
0.28
22.2 (75,817)
20.8 (69.5)
50
All
1100 (2300)
11.77
0.57
27.7 (94,600)
20.8 (69.5)
60
All
1300 (2800)
13.96
0.93
29.6 (101,089)
21.1 (70.0)
70
All
1500 (3200)
14.43
1.00
34.5 (117,824)
23 (73.4)
80
All
1700 (3700)
14.93
1.04
35.6 (121,580)
24.7 (76.5)
90
All
2000 (4100)
15.58
1.25
36.5 (124,654)
79.0 (26.1)
2
100
All
2200 (4600)
16.17
1.55
37.9 (129,435)
27.1 (80.7)
2
1
 In this case, the compressor will cycle because its speed is down to the minimum of 35 Hz.
The minimum fan speed for the InRow mode is 30%; the minimum fan speed for HACS and RACS mode is 40%.
2
 SA temperature is above 25° C (77° F)
Note: Outdoor temperature is 35° C (95° F)
Note: For ACRD500 series, reduce airflow and cooling capacity specifications by 7% for cooling units run at low input voltage (380 V).