Installation 
12
Page
 
Improper venting of this appliance can result in excessive levels of carbon 
monoxide which can result in severe personal injury or death. 
 
Improper installation can cause nausea or asphyxiation, severe injury or death from 
carbon monoxide and flue gases poisoning. Improper installation will void product 
warranty.
 
When installing the vent system, all applicable national and local codes must be 
followed. If you install thimbles, fire stops or other protective devices and they 
penetrate any combustible or noncombustible construction, be sure to follow all 
applicable national and local codes.
 
VENTING INSTRUCTIONS 
‐General‐
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
The water heater must be vented in accordance with the section “Venting of Equipment" of the latest 
edition of the National Fuel Gas Code: ANSI Z223.1/NFPA 54 in the United States and/or Section 7 of the 
CAN/CSA  B149.1  Natural  Gas  and  Propane  Installation  Code  in  Canada,  as  well  as  applicable  local 
building codes.
 
Hydro‐Smart recommends the “T‐Vent” line manufactured by TAKAGI (Refer to “T‐Vent” brochure for 
details). However, the following are also UL listed manufacturers: ProTech Systems Inc. (FasNSeal), Flex‐
L Inc., Z‐Flex Inc. (Z‐Vent III), Metal‐Fab Inc., and Heat‐Fab Inc. (Saf‐T Vent). 
 
 
General rules for venting water heaters are:  
  Place the water heater as close as possible to the vent terminator. 
  The vent collar of the water heater must be fastened directly to an unobstructed vent pipe. 
  Do not weld the vent pipe to the water heater’s vent collar.  
  Do not cut the vent collar of the unit. 
  The vent must be easily removable from the top of the water heater for normal service and 
inspection of the unit. 
  The water heater vent must not be connected to any other gas appliance or vent stack. 
  Avoid using an oversized vent pipe or using extremely long runs of the pipe. 
  For rooftop venting, a rain cap or other form of termination that prevents rain water from 
entering into the water heater must be installed. 
  Do not common vent or connect any vent from other appliances to the water heater vent. 
 
General rules for vent terminations:  
  Avoid locating the water heater vent terminator near any air intake devices. These fans can 
pick up the exhaust flue products from the water heater and return them to the building. 
This can create a health hazard. 
  Locate the vent terminator so that it cannot be blocked by any debris, at any time. Most 
codes require that the terminator be at least 12 inches above grade, but the installer may 
determine if it should be higher depending on the job site condition and applicable codes. 
  A proper sidewall terminator is recommended when the water heater is vented through a 
sidewall. 
  Regarding the clearances from the exhaust terminator to the air inlet or opening, refer to 
the next few pages. 