Size the gas pipe appropriately to supply the necessary volume of gas required for 
the water heater using ANSI233.1/NFPA 54 in the USA or CAN/CSA B149.1 in Canada 
or local codes.  Otherwise, flow capabilities and output temperatures will be limited. 
 
Check that the type of gas matches the rating plate first. 
 
Ensure  that  any  and  all  gas  regulators  used  are  operating  properly  and 
providing gas  pressures within the specified range shown below. Excess gas 
inlet pressure may cause serious accidents. 
 
Conversion of this unit from natural gas to propane or vise versa will  void all 
warranty.  Contact  your  local  distributor  to  get  the  correct  unit  for  your  gas 
type.    The  manufacturer  is  not  liable  for  any  property  and/or  personal 
damage resulting from gas conversions. 
 
GAS SUPPLY AND GAS PIPE SIZING
 
‐General‐ 
 
 
 
 
 
 
 
 
 
 
 
  The minimum and maximum inlet gas pressures are: 
Gas type 
Inlet gas pressure 
Natural Gas 
Min. 5.0” WC – Max. 10.5” WC 
Propane 
Min. 8.0” WC – Max. 14.0” WC 
 
  Gas  pressure  above  this  specified  range  for  the  water heater  and/or  insufficient  gas  volume  will 
adversely  affect  performance.    These  pressures  are  measured  when  the  water  heater  is  in  full 
operation. 
  Inlet gas pressure must not exceed the above maximum values; gas pressure above the specified 
range will cause dangerous operating conditions and damage to the unit.   
  Until testing of the main gas line supply pressure is completed, ensure the gas line to the water 
heater is disconnected to avoid any damage to the water heater. 
 
 
 
‐Gas connections‐ 
1. 
Install a manual gas shut‐off valve between the water heater and the gas supply line.   
2. 
When the  gas  connections  are  completed,  it  is necessary  to  perform  a  gas  leak  test  (see  below) 
either by applying soapy water to all gas fittings and observing for bubbles or by using a gas leak 
detection device.   
 
The water heater and its individual shutoff valve must be disconnected from the gas supply 
piping system during any pressure testing of that system at test pressures in excess of 1/2 psi 
(3.5 kPa). 
 
The water heater must be isolated from the gas supply piping system by closing its individual 
manual  shutoff  valve  during  any  pressure  testing  of  the  gas  supply  piping  system  at  test 
pressures equal to or less than 1/2 psi (3.5kPa). 
3. 
Always purge the gas line of any debris and/or water before connecting to the gas inlet. 
 
 
 
 
 
 