HP Performance Optimized Data Center (POD) 240a Manuel D’Utilisation

Page de 93
 
Environmental control system  60 
 
Callout 
Sensor 
Quantity per 
hot aisle 
Description 
Temperature sensors 
 
Monitor the temperature in various locations 
throughout the hot aisle of the HP POD 240e 
NA 
 
Report data to the ECS 
Hot aisle pressure sensor 
probes 
12 
 
Monitor and report hot aisle pressure 
 
Report data to the AHU controllers 
Hot aisle temperature sensor 
probes 
12 
 
Monitor and report hot aisle temperature 
 
Report data to the AHU controllers 
 
Outdoor air sensors 
There is one sensor mounted on each Adiabatic unit that monitors the temperature and humidity of the 
outdoor air. Each sensor reports the data to the AHU controller. 
 
Adiabatic units 
Each IT section of the HP POD 240e NA has six Adiabatic units that maintain the differential pressure and 
temperature parameters within the HP POD 240e NA. 
For more information about the required power for the Adiabatic units, see "Power distribution: Adiabatic 
system (on page 
)." 
 
Controlling the hot aisle fans 
There are 10 exhaust fans located in the hot aisle of the HP POD 240e NA. 
Side view shown 
 
The HP POD 240e NA fans operate at variable speeds (0-100%) to maintain predetermined parameters 
programmed into the AHU. For more information about the fan mode, see "AHU theory of operation (on 
page 
)".