HP Performance Optimized Data Center (POD) 20cp Manuel D’Utilisation

Page de 86
 
Component identification  12 
Electrical power component identification 
Front view shown 
 
 
Item 
Component 
Description 
Demarcation box
1
 
Customer communication connection point for the following 
components: 
 
ECS 
 
Access control 
 
Phone 
Fire box
1
 
Connection location for fire emergency and VESDAnet signals 
480/415 transformer 
cabinet
2
 
Converts main power from 480V to 415V for POD operation 
380-415 VAC WYE, 
3-phase, 320 A 
Feed A and B power for IT critical loads busways and house power 
 
1
The demarcation box and the fire box are communication data points that are provided on the POD by HP. Connecting 
these data points is the responsibility of the customer, unless an approved Statement of Work is initiated. 
2
This cabinet is designed for two transformers. The transformers are an optional component that might not be included. 
Main breaker locations