HP Performance Optimized Data Center (POD) 20cp Manuel D’Utilisation

Page de 86
 
Power, electrical, and controls  32 
Side view shown 
 
Disabling power 
 
To disable power to a single PDU, open the drop box breaker that powers the PDU, and then disconnect 
the PDU from the drop box. 
 
To disable power to a single rack, open the drop box breakers that power each of the PDUs installed 
in that rack. 
 
To disable power to a single busway, open the appropriate breaker for that busway on the 
corresponding electrical busway panel on the HP POD 20c exterior. 
 
To disable power to all racks, open the breaker for each busway on the corresponding electrical panel 
on the HP POD 20c exterior. 
 
Power configurations 
  
 
IMPORTANT:
  Different PDUs can alter the average power capacity per rack. 
  
 
Configuration  Number of 3-phase 
PDUs per HP POD 
20c 
Number of drop 
boxes per HP POD 
20c 
Average power 
capacity per rack 
Total HP POD 20c 
power capacity 
Non-redundant  20 
10 
28.8 
288 kW* 
Redundant 
20 
10 
14.4 
144 kW* 
 
*The HP POD 20c is electrically limited to N = 288 kW / 2N = 144 kW. 
 
Rack power 
Power is provided to each rack by PDUs and drop boxes. The PDUs are powered by the drop boxes attached 
to each electrical busway. For more information about electrical busway drop boxes, see the HP 
Performance Optimized Datacenter 20c Maintenance and Service Guide