HP Performance Optimized Data Center (POD) 20cp Manuel D’Utilisation
Power, electrical, and controls 32
Side view shown
Disabling power
•
To disable power to a single PDU, open the drop box breaker that powers the PDU, and then disconnect
the PDU from the drop box.
•
To disable power to a single rack, open the drop box breakers that power each of the PDUs installed
in that rack.
•
To disable power to a single busway, open the appropriate breaker for that busway on the
corresponding electrical busway panel on the HP POD 20c exterior.
•
To disable power to all racks, open the breaker for each busway on the corresponding electrical panel
on the HP POD 20c exterior.
Power configurations
IMPORTANT:
Different PDUs can alter the average power capacity per rack.
Configuration Number of 3-phase
PDUs per HP POD
20c
Number of drop
boxes per HP POD
boxes per HP POD
20c
Average power
capacity per rack
capacity per rack
Total HP POD 20c
power capacity
power capacity
Non-redundant 20
10
28.8
288 kW*
Redundant
20
10
14.4
144 kW*
*The HP POD 20c is electrically limited to N = 288 kW / 2N = 144 kW.
Rack power
Power is provided to each rack by PDUs and drop boxes. The PDUs are powered by the drop boxes attached
to each electrical busway. For more information about electrical busway drop boxes, see the HP
Performance Optimized Datacenter 20c Maintenance and Service Guide.
Performance Optimized Datacenter 20c Maintenance and Service Guide.