HP Performance Optimized Data Center (POD) 20cp Manuel D’Utilisation

Page de 86
 
Environmental control system  53 
The Advanced System Configuration screen displays fan current setpoints, calibration options, and other 
details about the HP POD 20c. 
 
Perform the following tasks on this screen: 
 
Calibrate the flowmeter. 
 
Calibrate the chilled water and differential pressure sensors. 
 
View the power configuration. 
 
Set the logging configuration. 
 
Configure the HP POD 20c serial number. 
 
Configure the switchboard serial number. 
You must select Save to store the parameter changes in the system configuration file. If you do not save your 
changes, the old parameters stored in the configuration file reload when the system starts. 
 
Setting the start-up alarm reset delay 
This option gives the POD time (in seconds) during a start-up to achieve at least minimum operating 
parameters prior to registering an alarm condition. 
To set the amount of time prior to registering an alarm condition: 
1. 
Select Reset alarms after startup time (sec). 
A keypad appears. 
2. 
Enter the time in seconds you want the alarms to reset after startup.