Removal and replacement procedures 42
Fire strobe light
The HP POD 40c NA contains an internal fire alarm strobe light in the cold aisle and an external fire alarm
strobe light at the standard personnel entry door.
strobe light at the standard personnel entry door.
You need a screwdriver for installation.
Removing the fire strobe light
1.
Remove the four screw cover plates (1).
2.
Remove the four screws securing the components (2), and then disconnect the wiring.
3.
Remove the electric sounder with strobe, the semi-flush plate, and the standard back box (3).