HP Performance Optimized Data Center (POD) 40cp Instruction De Maintenance

Page de 79
 
Specifications  72 
Feature 
Specification 
Non-operating temperature*  -29ºC to 54ºC (-20ºF to 130ºF) 
Operating humidity 
 
0% to 100% external 
 
10% to 90% non-condensing internal 
Non-operating humidity* 
 
5% to 95% relative non-condensing 
 
39ºC (102ºF) maximum wet bulb 
temperature 
Operating altitude 
-76.2 m to 3,048 m (-250 ft to 10,000 ft) 
Non-operating altitude 
-76.2 m to 9,144 m (-250 ft to 30,000 ft) 
 
*For non-operating specifications, consider the temperature of computer and IT equipment inside the HP POD 40c NA. 
 
Optional features specifications 
  
Feature 
Specification 
Fire suppression 
3M Novec 1230 fire extinguishing system provided in two canisters (main and reserve) 
Card reader 
12-key pad with 125 KHz proximity and 13.56 MHz contactless smart card 
Humidifier 
Provides 2-8 lb/hr of water vapor into cold aisle to maintain POD environment within 20% 