DR4300 Circular Chart Recorder Product Manual 
 
43
2.6.3  Transmitter Power Out 
Introduction 
A recorder model is available that provides +24 Vdc power out to a transmitter.  
Procedure 
Refer to Figure 2-17 and follow the procedure in Table 2-15 to wire the transmitter power out.  
 
Table 2-15  Transmitter Power Out Wiring 
Step Action 
ATTENTION  To avoid damaging the recorder, be sure that you install the power wires into the 
correct screw terminals as shown in Figure 2-9 an
d Figure 2-10. 
Turn off the power to the recorder. 
Open the recorder door. Loosen the captive screw in the chart plate and swing the plate out. 
Locate the DC OUT terminal block on the Transmitter Power Module, located above the 
printed circuit assembly (PCA) for pen 1. (See Figure 2-17.) 
Run the output wires through the appropriate conduit hole (see Figure 2-7 and Figure 2-8). 
Refer to Table 2-6 for acceptable wire bundling. 
Strip 1/4-inch maximum of insulation from the end of each wire and form end to fit under a 
screw connection. 
Insert the wires under the appropriate screws for the transmitter power out as shown in the 
figure. Tighten the screws to secure the wires.