Honeywell VCR DCP200 Manuel D’Utilisation

Page de 184
DCP200 Profile Controller & Recorder - Product Manual
51-52-25-150, Issue 1 – April 2009
Modbus Parameters
Page 101
Parameter Name
Modbus Address
Access
Values
(Dec)
(Hex)
14
Event 1 AND Alarm 1. Direct Acting
15
Event 1 AND Alarm 1. Reverse Acting
16
Event 2 AND Alarm 2. Direct Acting
17
Event 2 AND Alarm 2. Reverse Acting
18
Event 3 AND Alarm 3. Direct Acting
19
Event 3 AND Alarm 3. Reverse Acting
20
Event 4 AND Alarm 4. Direct Acting
21
Event 4 AND Alarm 4. Reverse Acting
22
Event 5 AND Alarm 5. Direct Acting
23
Event 5 AND Alarm 5. Reverse Acting
Setpoint Parameters
Parameter Name
Modbus Address
Access
Values
(Dec)
(Hex)
Setpoint Minimum
3944
0x0F68
R/W
Valid between Scale Range Maximum and Minimum
Setpoint Maximum
3945
0x0F69
R/W
Valid between Scale Range Maximum and Minimum
Local Setpoint 1 
Value
3960
0x0F78
R/W
Valid between Setpoint Maximum and Minimum
Local Setpoint 1 
Offset
3961
0x0F79
R/W
Setpoint is always limited within Setpoint Maximum 
and Minimum
Local Setpoint 2 
Value
3962
0x0F7A
R/W
Valid between Setpoint Maximum and Minimum
Local Setpoint 2 
Offset
3963
0x0F7B
R/W
Setpoint is always limited within Setpoint Maximum 
and Minimum
Setpoint Selection 
Method
4000
0x0FA0
R/W
Value
Setpoint Selection Method
0
Local Setpoint 1 only
1
Selected by Digital Input A
2
Selected by Digital Input B
3
Alternate Setpoint only
4
Operator or Comms selectable
Alternate Setpoint 
Source
4001
0x0FA1
R/W
Value
Alternate Setpoint Source
0
Local Setpoint 2
1
Remote Setpoint from Auxiliary Input A
2
Remote Setpoint from Auxiliary Input B
Auxiliary Input A 
Scale Minimum
4073
0x0FE9
R/W
Valid between Setpoint Maximum and Minimum
Auxiliary Input A 
Scale Maximum
4074
0x0FEA
R/W
Valid between Setpoint Maximum and Minimum
Auxiliary Input A 
Offset
4075
0x0FEB
R/W
Setpoint is always limited within Setpoint Maximum 
and Minimum
Auxiliary Input A 
Value
4076
0x0FEC
RO
The value of analogue Auxiliary Input A
Auxiliary Input B 
Scale Minimum
4078
0x0FEE
R/W
Valid between Setpoint Maximum and Minimum
Auxiliary Input B 
Scale Maximum
4079
0x0FEF
R/W
Valid between Setpoint Maximum and Minimum