Modbus Parameters
51-52-25-150, Issue 1 – April 2009
Parameter Name
Modbus Address
Access
Values
(Dec)
(Hex)
Alarm 5 Type
6208
0x1840
R/W
Value
Alarm 5 Type
0
Process High Alarm
1
Process Low Alarm
2
Deviation Alarm (SP-PV)
3
Band Alarm
4
Loop Alarm
5
Input/Sensor Break Alarm
6
Auxiliary Input A Break Alarm
7
Auxiliary Input B Break Alarm
Alarm 5 Value
6209
0x1841
R/W
Limited by the input range maximum and minimum for 
Alarm types 0 and 1. Limited by the input span for
alarm types 2 and 3. Not used for alarms 4 to 7.
Alarm 5 Hysteresis
6210
0x1842
R/W
Limited by the input span
Alarm 5 Inhibit 
Enable/disable
6211
0x1843
R/W
Value
Alarm 5 Inhibit Enable
0
Disabled
1
Enabled
Alarm 5 Status
6212
0x1844
RO
Value
Alarm 5 Status
0
Inactive
1
Active
Alarm 5 Inhibit 
Status
6213
0x1845
RO
Value
Alarm 5 Inhibit Status
0
Not Inhibited
1
Inhibited
Recorder & Clock Parameters
Parameter Name
Modbus Address
Access
Values
(Dec)
(Hex)
Recording Sample 
Interval
7550
0x1D7E
R/W
Value
Recording Sample Interval
0
Every Second
1
Every 2 Seconds
2
Every 5 Seconds
3
Every 10 Seconds
4
Every 15 Seconds
5
Every 30 Seconds
6
Every Minute
7
Every 2 Minutes
8
Every 5 Minutes
9
Every 10 Minutes
10
Every 15 Minutes
11
Every 30 Minutes
Recording Mode
7551
0x1D7F
R/W
Value
Recording Mode
0
Record until memory used
1
Continuous FIFO buffer
Start Stop 
Recording
7552
0x1D80
R/W
Value
Operator Start/Stop Recording
0
Stop Recording