Electrical Installation
Page 31
Option Slot 2 – Single SSR Driver Output Module
If option slot 2 is fitted with a single SSR driver output module, make connections as 
illustrated. The solid-state relay driver is a 0-10V DC signal, load impedance must be no less 
than 500 ohms. SSR driver outputs are not isolated from the signal input or other SSR driver 
outputs.
Figure 20.
Option Slot 2 – Single SSR Driver Module
Option Slot 2 – Dual SSR Driver Output Module
If option slot 2 is fitted with a dual SSR driver output module, make connections as 
illustrated. The solid-state relay drivers are a 0-10V DC signal, load impedance must be no 
less than 500 ohms. SSR driver outputs are not isolated from the signal input or other SSR 
driver outputs.
Figure 21.
Option Slot 2 – Dual SSR Driver Module
Option Slot 2 - Triac Output Module
If option slot 2 is fitted with a Triac output module, make connections as shown. This output 
is rated at 0.01 to 1 amp @ 280V AC 50/60Hz. A snubber should be fitted across inductive 
loads to ensure reliable switch off the Triac.
Figure 22.
Option Slot 2 - Triac Module