Honeywell Home Theater Server T755U Manuel D’Utilisation

Page de 40
T775U SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLER
62-0255—09
28
Default: 60°F (16°C)
Range: -40°F to 248°F (-40°C to 120°C)
3. Press the u button to accept the value and display 
the menu.
Fig. 62. Program - Sensor.
2.1.3. SENSOR
This sub-menu choice is only available on the T775U2016 
model.
1. From the menu, use the p and q buttons to highlight 
SENSOR A or SENSOR B.
2. Press the u button to accept the sensor selection 
and display the next option.
Fig. 63. Program - Throttling Range or Differential.
2.1.5. THROTTLING RANGE or 
DIFFERENTIAL
Throttling Range displays for Modulating outputs. 
Differential is used for the Relay outputs.
1. From the menu, use the p and q buttons to highlight 
THROT RNG or DIFFERNTL.
2. Press the u button to display the throttling range 
value.
3. Use the p and q buttons to increase/decrease the 
desired value. 
Default: 20°F (-6.6°C)
Range: 1°F to 150°F (1°C to 66°C)
4. Press the u button to accept the value and display 
the next option.
The Throttling Range brackets the setpoint setting, e.g., if 
the setpoint is 72°F and the throttling range is 10°F, then 
the effective throttling temperature range is 67°F to 77°F.
In heating mode, the Differential is below the setpoint. The 
relay de-energizes when the temperature rises to the 
setpoint. As the temperature drops to the setpoint minus 
the Differential, the relay energizes.
In cooling mode, the Differential is above the setpoint. The 
relay de-energizes when the temperature falls to the 
setpoint. As the temperature rises to the setpoint plus the 
Differential, the relay energizes.
Fig. 64. Program - Action.
2.1.6. ACTION
1. From the menu, use the p and q buttons to highlight 
ACTION.
Default: HEAT
2. Press the u button to display the action selections.
3. Use the p and q buttons to select the desired value.
4. Press the u button to accept the highlighted selec-
tion and display the next option. 
PROGRAM
 MOD 
1
 SENSOR
MENU
PROGRAM
MOD 1
SENSOR
SELECT
SENSOR
FOR 
MOD 1
SENSOR A
SENSOR B
M28660
ENTER
THROTLLING
RANGE FOR 
MOD 1
PROGRAM
 MOD1
 
THROT RNG
MENU
PROGRAM
MOD 1
THROT RNG
20
F
M24582
PROGRAM
 MOD 
1
 ACTION
MENU
PROGRAM
MOD 1
ACTION
SELECT
ACTION
FOR 
MOD 1
HEAT
COOL
REV ACT
DIR ACT
HUMID
DEHUMID
M24583