ADJUSTABLE FEATURES 
TRANSISTOR PUMP CONTROLS 
 
 
Page 64  
 
January 2000 
Section 6.6 Setup Functions for Hydraulic Pump Control 
 
FUNCTION 1:  
NOT APPLICABLE 
 
 
This function is not applicable to this type of control and 
should not be adjusted. 
 
FUNCTION 2:   
INTERNAL RESISTANCE  
 COMPENSATION 
START 
 (Push 
2) 
 
 
This function allows for the adjustment of the current level 
at which the internal resistance compensation feature 
(Function 16) will take effect. 
 
Range   
0 to 1325 amps   
Setting   
52 to 255 
Resolution 
6.5 amps per set unit 
 
Example: Setting of 72 =  (72-52) x 6.5 = 130 amps  
 
FUNCTION 3:  
CONTROLLED ACCELERATION  
 (Push 
3) 
 
 
This function allows for the adjustment of the rate of time it 
takes for the control to accelerate to 96% applied battery 
voltage to the motor on hard acceleration.   
 
Range    
0.1 to 5.5 seconds 
Setting   
0 to 255 
Resolution 
0.021 seconds per set unit 
 
Example: Setting of 20 = 0.52 seconds C/A 
 
FUNCTION 4:  
 CURRENT LIMIT 
 (Push 
4) 
 
 
This function allows for the adjustment of the current limit 
of the control. The rating of the control will determine the 
range of adjustment for this function. Please refer to the 
OEM operating instructions for the control used in your 
vehicle. 
 
Range   
See OEM control C/L curves 
Setting   
0 to 255 
 
Example: 0 = min. current, 255 = max. current 
 
FUNCTION 7:   
INTERNAL RESISTANCE 
 COMPENSATION 
RATE 
 (Push 
7) 
 
This function allows for the adjustment of the rate of time it 
takes for the control to add the internal resistance 
compensation voltage that is applied to the motor. This 
function will add 0.375 volts to the motor at the rate of time 
adjusted until the total IR compensation voltage has been 
added.  
 
Range    
0.0015 to 0.383 seconds 
Setting   
0 to 255 
Resolution 
0.0015 seconds per set unit 
 
Example: Setting of 20 = 0.032 seconds  
For example, if you had selected 2.08 volts from Function 16 
to be added to the motor, it would take 0.18 seconds to add 
a total of 2.08 volts.  (2.08/0.375)=0.032 
 
FUNCTION 11: 
SPEED LIMIT 1 (SL1) 
 (Push 
11) 
 
This function allows for the adjustment of the speed limit 
(maximum battery volts to the motor) when the SL1 limit 
switch input signal is received by the control card.   SL1 
limit switch is a normally open switch connected to battery 
negative, the switch closing enables speed limit. 
 
Range   
0% to 100% battery volts 
Setting   
0 to 255 
Resolution 
0.375 volts per set unit 
 
Example: Setting of 50=18.75 volts  
 
FUNCTION 12: 
SPEED LIMIT 2 (SL2) 
 (Push 
12) 
 
 
 
Same as Function 11 except using SL2 limit switch for input. 
 
FUNCTION 13: 
SPEED LIMIT 3 (SL3) 
 (Push 
13) 
 
Same as Function 11 except using SL3 limit switch for input. 
 
FUNCTION 14: 
NOT  APPLICABLE 
 
 
This function is not applicable to this type of control and 
should not be adjusted. 
 
FUNCTION 16: 
SPEED / TORQUE  COMPENSATION 
 
(Push CONT  1) 
This function is used to stabilize pump speed at heavy 
loads.   The voltage selected will be added to the motor at 
each 100 amp increment starting at the value set in 
Function 2.  The voltage compensation selected will be 
added in increments of 0.375 volts until the entire voltage is 
added.  For example,  a setting of 2 will be added in 30 steps 
Note:  The following functions have function numbers 
larger than the numbers on the Handset keyboard.  To 
access these functions, push the CONT key and the 
number shown in the following instructions at the same 
time. THE KEY SWITCH MUST BE OPEN.