Inspection and Installation
13
Liebert
®
 MC
Figure 8
Equipment recommended for handling a Liebert condenser
3.2
Handling Unit on the Skid
Transport unit using a forklift or a crane with sling and spreader bars.
• If using a fork lift, make sure the forks (if adjustable) are spread to the widest allowable distance 
to still fit under the skid.
• Type of fork lift used will be dependent on the terrain the unit to be moved across during 
handling. 
• Minimum fork lift fork length for use on 1 and 2 fan units to be 48" (1219mm).
• When moving the packaged unit, do not lift the unit any higher than 6"(152mm) off the ground. If 
circumstances require the unit to be lifted higher than 6" (152mm), great care must be exercised 
and all personnel not involved in moving the unit must be at least 20' (5m) from the lift point of 
the unit.
Figure 9
Forklift position with one-fan or two-fan condensers 
• When using a forklift to off-load or move for installation, it is recommended to lift one narrow end 
off the ground no more than 6" (152mm). Use the forklift to push or pull the unit.
• When using a crane to lift the unit from a flat bed or to move for installation, using slings rated 
for the unit weight is recommended.
• Spreader bars are to be used for sling stability and to prevent unit pinching. Make sure spreader 
bars are wider than the unit.
• Slings are to be placed near the ends of the unit, under the top deck boards of the skid.
3.3
Unit Storage
• Store the fan in the original shipping packaging in a dry area protected from the weather, or 
protect it from dirt and weather until final installation.
• Avoid temperatures below -30°F (-34°C) and above 150°F (65°C).
• Avoid storing the Liebert MC condenser for longer than one year.
Forklift
Crane
Lift Beam, Slings
and Spreader Bars
308111
Pg. 1, Rev. 1
308111