Piping
Liebert
®
 MC
34
5.4
Equipment Application Guidelines
Pump-down must be disabled on the indoor unit when using the Liebert MC condenser, due to the 
reduced volume in the condenser coil. When applying the Liebert MC condenser to existing Liebert 
indoor units, Emerson
®
 recommends adding a discharge line check valve and crankcase heater to 
provide suitable compressor protection. Additional liquid line Schrader ports are required at the 
indoor unit to properly charge systems with Liebert MC condensers applied.
5.5
Refrigerant Oil Addition Procedures
Consult the user manual for the indoor unit to determine whether additional oil is required for each 
circuit. Factors such as compressor, condenser type, piping lengths, and total circuit refrigerant 
charge influence this requirement.
5.6
System Dehydration/Leak Test
Procedures for leak check and evacuation of the entire refrigeration system are contained in the 
indoor unit’s installation manual. Use the proper manual section corresponding to the winter control 
system used on the condenser (with or without Liebert Lee-Temp
 or Liebert DSE
 receivers) and the 
refrigerant to be charged into the system.
5.7
Liebert MC Condenser Charging, Units with Liebert Lee-Temp
 Systems
Consult the indoor unit’s manual for charging systems with Liebert Lee-Temp receivers. These 
procedures will be identical to systems with fin/tube condenser coils, but the refrigerant volumes will 
be much lower. Consult Tables 10 and 11 for condenser with Liebert Lee-Temp refrigerant required.
5.8
Liebert MC Condenser Charging with Liebert DSE
 Units
Consult the Liebert DSE’s manual (SL-18925) for charging Liebert DSE systems. All Liebert DSE 
units require installation of a Liebert DSE receiver on each condenser circuit, with or without a 
Liebert EconoPhase pump module installed. Consult Table 11 for condenser and receiver refrigerant 
requirements.
Table 12
Interconnecting piping refrigerant charge
Line Size
O.D., in.
R-407C, lb/100 ft. (kg/30m)
R-410A, lb/100 ft. (kg/30m)
Hot Gas Line
Liquid Line
Hot Gas Line
Liquid Line
3/8
3.7 (1.7)
1/2
6.9 (3.1)
5.0 (2.1)
5/8
2.2 (1.0)
11.0 (5.0)
1.1 (0.51)
10.0 (4.2)
3/4
3.1 (1.3)
15.7 (7.1)
1.5 (0.67)
13.0 (5.7)
7/8
4.5 (1.9)
23.0 (10.4)
2.3 (1.0)
21.0 (9.5)
1-1/8
7.8 (3.5)
39.3 (17.8)
3.9 (1.8)
34.9 (15.6)
1-3/8
11.8 (5.4)
59.8 (27.1)
5.5 (2.5)
53.2 (23.8)
1-5/8
16.7 (7.6)
Charge based on Type ACR/Type L copper pipe
Source: DPN002411, Rev. 3