Control Operation
Liebert
®
 MC
42
8.0
C
ONTROL
 O
PERATION
The Liebert MC Premium Efficiency Control takes approximately 30 seconds to boot up once power is 
applied to the condenser. The LED on the Premium Efficiency Control Board reads “888” while the 
board is booting up. Once the control has booted up, the display shows “F00” and then the value for 
F00. With the control operational, the condenser fan(s) turn in less than 5 seconds after receiving a 
signal from the indoor unit that the compressor(s) are On. Consider using UPS equipment on both 
data center cooling units and Liebert MC condensers to maintain uninterrupted cooling capability.
For the first 60 seconds of operation after the compressor turns on, the condenser fan(s) will run at a 
fixed speed, set at the factory, based on ambient temperature: faster at higher temperatures, slower 
at lower temperatures. After 60 seconds, the control adjusts the fan speed based on the liquid 
pressure transducer. If the liquid pressure transducer fails, the condenser uses temperature sensors 
to control the fan speed based on the liquid line temperature. The condenser fans continue to operate 
for approximately 30 seconds after compressors turn Off.
The Liebert MC fans have various alarm conditions, such as loss of voltage and loss of control signal, 
that will stop the condenser fans. Once the alarm condition is no longer present the Liebert MC fans 
will turn on automatically if compressors are On.
8.1
Premium Efficiency Control Board and Interface
The Liebert MC Premium Efficiency Control board has a stacked board arrangement. There are three 
seven-segment LED’s and four keys as human machine interface (see Figure 24).
Figure 23 Premium efficiency fan control board
NOTE
Indicator lights should be on, to indicate signal is present. See Figure 23, #1, 2 and 3.
301471
Pg. 2, Rev. 3
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Spare Digital
Outputs (Not
Used)
Call for
Cooling
Remote
Shutdown
Fan
Contactor
Output
Mother
Board
24VAC
Earth
Ground
Fan 4
Fan 3
Fan 2
Fan 1
CPU
Board
RS485
Communication
to Fans
Spare Analog
Outputs (Not Used)
Communication
from
indoor unit
Communication
from
indoor unit
CANbus
Service
Pressure
Inputs
Circuit 1
Circuit 2
Circuit 1
Circuit 2
Ambient
Temperature
Inputs
Alarm & Shutdown
Circuits
Ethernet and CANbus addressing
and signal indication
Indicator Lights: ON - Signal Present
Indicator Lights:
ON - Signal
Present
Control Fuses
RS485 Service
Terminal
BAR CODE
24VAC
CAUTION
For Continued Protection Against Risk of Fire,
Replace Only With Same Type and Rating of Fuse
ACM01M1
VER:A02
2010.08.10
BAR CODE
Human
Machine
Interface
(HMI)
Circuit 1
Circuit 2
F3 T3.15A, 250VAC
F2 T3.15A, 250VAC
ACM01U1 VER:A03 2010.08.10
1
1
Fuses are rated to 3A/250V
#1 
#3
#2
J5