Emerson DC-DC Converter Module Mounting Shelf DCS4830 Manuel D’Utilisation

Page de 17
SAG584622000
 
System Application Guide 
Issue AB, November 18, 2009 
Spec. No. 584622000 (Model DCS4830) 
 
Page 10 of 17 
 
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy 
Systems, North America, Inc.  Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. 
SPECIFICATIONS 
1.1 Output 
Ratings 
1.1.1 Voltage:  Nominal -48 volts DC, positive ground, non-adjustable. 
1.1.2 Current:
  10 amperes per DC-DC Converter Module, up to a total of 30 amperes per DC-DC 
Converter Mounting Shelf when three (3) Converter Modules are installed. 
1.1.3 Regulation 
(A) Static:  Steady state output voltage remains within ±1 volt of the pre-adjusted voltage for 
any load current from no load to full load and over the specified input voltage range. 
(B) Dynamic:
  For a step load change of 50% within the range of 10% to 100% of full rated 
current, the maximum voltage transient will not exceed 5% of the initial steady state voltage. 
1.1.4 Filtering:
  With at least 10% of rated full load on the output (-20°C to +65°C). 
(A) 
Voice band noise is less than 32 dBrnC when measured with a noise meter using 600 ohm 
bridged input and C-message weighting. 
(B) 
Wide band noise does not exceed 250 millivolts peak to peak over the frequency range of 0 
Hz to 20 MHz. 
(C) 
Wide band noise does not exceed 30 millivolts rms over the frequency range of 0 Hz to 20 
MHz (as measured with an HP3400A true rms voltmeter). 
(D) 
Noise below –20°C is slightly higher. 
1.1.5 Output 
Distribution:
  Two (2) 6-Position GMT Fuse Modules are provided for connecting DC 
output load leads.