DT between Room Air / Outdoor—Sets the delta that must be achieved between the outdoor 
temperature and either the return setpoint or return actual reading to enable the Liebert Air 
Economizer.
DT between Room / FC Type—Determines the method to activate the water circuit on dual-cool 
and free-cool units. When this parameter is set to “Contact,” a dry contact closure can be used to 
activate the free cooling circuit. When this parameter is set to “Value,” the delta between the water 
temperature of the free-cooling circuit and the actual room temperature are compared.
DT between Room Air / FC Fluid—Sets the delta between the actual room temperature and the 
free-cooling fluid temperature to determine if cooling can be provided.
Minimum CW Temp—Enables the temperature at which free-cooling can operate independently 
without assistance of the compressor circuit.
Minimum CW Temp Value—Sets the water temperature at which 100% free-cooling can be 
provided to handle the full room load. When the fluid temperature is below this setting then the 
compressors will no longer turn on until the water temperature is above the minimum CW Temp.
Lockout FC at FC Fluid below—The temperature that turns off the free-cooling circuit when the 
water temperature is too low. This setting prevents frost from building up on the free-cooling pipes 
when the outdoor ambient is extremely low.
Transition Change—Applied over the “Cooling Filter at 0% / 100%” when the cooling signal makes 
the transition between cooling and dehumidification. This will smooth the cooling capacity changes 
between dehumidification and cooling.
Figure 11 Service/Economizer, page 1 of 3
Enable Economizer—Sets the Liebert Air Economizer operation to one of the following modes. 
These selections only determine if the Liebert Air Economizer is available for use; they do not 
determine or override damper position. Damper position is always controlled by the sensor set to 
control temperature (i.e., Return / Supply Sensor)
• Yes: This parameter will operate the Liebert Air Economizer based on the outdoor sensor reading 
and will allow the Liebert iCOM to determine if the conditions are within the acceptable range of 
operation.
• NO: This parameter will disable the Liebert Air Economizer and will not allow Liebert Air Econo-
mizer to operate even if the outdoor conditions are acceptable.
• Remote: This parameter will enable the Liebert Air Economizer and ignore the outdoor Liebert 
iCOM sensor even if the conditions are outside the range of operation.
Economizer (page 1 of 3)
to change parameter
to confirm
to select parameter
for next/previous unit
then 
UNIT   01
SA01
SA02
SA03
SA04
SA05
SA06
SA07
SA08
SA09
SA10
SA11
PASSWORD   (Actual Level  3)
????
Enable Economizer
Yes, No, Remote
Status
Min
Act Max
Humidity Ratio
OK/NOK
5.7
8.0 11.0
Wet Bulb Temp
OK/NOK
55°F
Outdoor Temp
OK/NOK
73°F
Stop ECO at Setpoint +
25°F
Economizer Mode
ON/OFF
Dewpoint (Calculated)
48°F
Economizer Override At 102°F
Delay After Fan Start
5 min