Emerson Dual Conversion Online UPS GXT3-6000RT208 Manuel D’Utilisation

Page de 52
Specifications
38
12.0 S
PECIFICATIONS
Table 7
UPS specifications—5000, 6000, 8000 and 10,000 models
Model Number
GXT3-5000RT208 GXT3-6000RT208 GXT3-8000RT208 GXT3-10000RT208
Model Rating
4000W/5000VA
4800W/6000VA
7200W/8000VA
9000W/10000VA
 Dimensions, Rack Mount, W x D x H
 
Unit, in. (mm)
16.9 x 26.1 x 6.8 (430 x 662 x 173)
16.9 x 26.5 x 10.3 (430 x 672 x 261)
 
Shipping, in. (mm)
26.1 x 33.1 x 13.2 (662 x 842 x 336)
24.1 x 32.8 x 16.7 (612 x 832 x 424)
 Weight lb (kg)
 
Unit, lb (kg)
56.2 (25.5)
78.3 (35.5)
 
Shipping, lb (kg)
 70.5 (32)
92.6 (42)
 
Input AC Parameters
 
Nominal Operating Frequency
 
50 or 60Hz (Factory Default is 60Hz)
 
Factory Default VAC
 
120/208VAC at 120 degrees
 
120/208VAC at 120 degrees
 
L1-L2 Factory Default Input Phase Angle
 
120 degrees
 
120 degrees
 
Allowable Input Phase Angle
120, 180, 240 degrees, auto-sensing on application of alternating current
(Restrictions for L-N voltages other than 120VAC)
 
Factory Default L1-N, L2-N VAC
 
120 VAC nominal
 
User Configurable L1-N, L2-N VAC
 
100/110/115/120VAC (can be modified with configuration program)
 
Input Frequency w/o Battery Operation
 
40 - 70 Hz
 
Input Power Connection
 
Hardwire Terminal Block 3W + G (L-L-N-G)
 
L1-N, L2-N Maximum Allowable VAC
150VAC
 
Output AC Parameters
 
Factory Default VAC
 
120/208VAC @ 120 degrees
 
L1-L2 Factory Default Output Phase Angle
 
120 degrees
 
Allowable Output Phase Angle
 
120, 180, 240 degrees, auto-sensing on initial application of input AC
 
Factory Default L1-N, L2-N VAC
 
120VAC nominal
 
User Configurable L1-N, L2-N VAC
 
100/110/115/120VAC, ±2%
 L1-N, L2-N, Operating Load Range
105% to 130%
1 Minute
131% to 150%
10 seconds
151% to 200%
1 second
>200% (impact load)
At least 5 cycles
 
Bypass Protection Limits
 
Disable Bypass Operation
 
If input voltage exceeds ±15% of the nominal voltage
 
Re-Enable Bypass Operation
 
If input voltage returns to within ±10% of nominal output voltage
 
Disable Bypass Operation
 
When the input frequency prevents synchronous operation
 
Environmental
 
Operating Temp, °F (°C)
 
Storage Temp, °F (°C)
5 to 122 (-15 to 50)
 
Relative Humidity
0% to 95%, non-condensing
 
Operating Elevation
Up to 10,000 ft. (3000m) at 77°F (25°C) without derating
 
Audible Noise less than 55dBA at 3.2ft. (1m) rear; less than 50dBA at 3.2ft. (1m) front and sides
 Agency
 Safety
UL 1778, c-UL Listed
 
RFI/EMI
FCC Part 15, Subpart B, Class A, FCC Class A
 
Surge Immunity
IEEE/ANSI C62.41 Category A & B
 
Transportation
ISTA Procedure 1A