Setup Program – Serial Connection                                               Thin Web Server 
 
 
4-4
 
Alarms - Email Address 
 
Alarms - ATS Power Manager Setting 
Alarms - Engine PM Details 
6.  Click the Email Address lower tab. Then enter the e-mail 
addresses (up to 5) of the persons whom you want 
notified of the selected alarms. Double check each e-mail 
address displayed in the five text boxes to verify that it 
has been typed correctly. 
Note: Make sure outgoing mailserver is configured 
properly and working. This functionality can be 
tested with third party e-mail testing programs. 
 
7.  Click the ATS Power Manager Setting lower tab. The 
Network 1 Power Managers (addresses) are displayed 
first. For each Power Manager (PM) address click the 
drop-down arrow and select the appropriate icon number 
associated with the PM.  If a Power Manager: 
  - is with an ATS, select icon 1.  
  - is with a circuit breaker, select icon 3 or 4.  
  - is not associated with an ATS or a CB, select icon 2
Then click View Network 2 Settings and select icons for 
those PMs. 
 
8.  Click the Engine PM Details lower tab. Network 1 & 2 
Engine Power Manager (addresses 33-36) are displayed. 
Enter a Description and Location for each PM. Then 
select the appropriate icon associated with each PM. 
Select if device is associated with CCM, EGCP, or both. 
 
9.  Click the Engine Power Manager Setting lower tab. 
Select the check boxes Status Inputs and/or Discrete 
Outputs
 that you want included in alarms monitoring.  
 
continued on the next page 
Ö 
 
 
Alarms - Engine Power Manager Setting