Thin Web Server                                                                                                                                           Troubleshooting 
 
 
Symptom 
Possible 
Problem 
Possible 
Cause 
Action Prevention 
13. Server setup 
program cannot 
upload / 
download 
configuration. 
Receiving an 
error message 
after upload / 
download. 
Corrupted 
TWS 
configuration 
file. 
 – TSSP & TWS program 
version mismatch. 
Same as item 4 
Same as item 4 
14. Serial Modbus 
communication 
is not working 
properly. 
 
Modbus 
master cannot 
communicate 
with TWS. 
 – TWS is not serially connected 
properly to the Modbus 
master. 
 – TSSP was not configured for 
serial Modbus 
communication. 
 – Incorrect serial cable adapter 
used for this application. 
 – Incorrect registers used by the 
Modbus master. 
 – Make sure to use the correct serial adapter to connect the  
Modbus master to the TWS. 
 – Only COM2 can be used for serial Modbus 
communication. 
 – Make sure to enable and set up serial communication to the 
TWS properly. 
 – Make sure to use only the register maps for TWS serial 
Modbus communication. 
 – Follow this Installation 
Manual for how to 
connect and implement 
Modbus communication 
in the TWS. 
 – Only use TWS Modbus 
communicaton register 
maps in designing GUI 
applicaton that will 
communicate to ASCO 
device through the 
TWS. 
 
15. TCP/IP open 
Modbus 
communication 
is not working 
properly. 
 
Modbus 
master cannot 
communicate 
with TWS. 
 – TWS was not configured for 
TCP/IP Modbus 
communication. 
 – Incorrect registers and 
addressing scheme used by 
the Modbus master. 
 – Make sure to enable and set up TCP/IP Modbus 
communication to the TWS properly through TSSP. 
 – Make sure to use only the register maps for TWS TCP/IP 
Open Modbus communication. 
 – TCP/IP Modbus communication of the TWS only renders 
data from serial devices connected to its COM3 & COM4 
ports. TWS does not render data from remote 72Es. 
 – Follow this Installation 
Manual for how to 
install the TWS and use 
the TSSP. 
 – Only use TWS Modbus 
communication register 
maps in designing GUI 
application that will 
communicate to ASCO 
device throught the 
TWS. 
16. Needed to reset 
alarm logs. 
 
 
 – Run your server setup program again, connect to the TWS. 
Go to UtilitiesServer File Management and delete 
the file C:\alarm.bin.  Refer to page 5-1.