Falcon MONITORING F110 Manuel D’Utilisation

Page de 36
www.rletech.com
32
970.484.6510
B
  Modbus Registers
40026
TL
Low Temperature (External Sensor 3)
Celsius x100
0-65535
40027
HC
Current Humidity (External Sensor 3)
% Relative Humidity
0-65535
40028
HH
High Humidity (External Sensor 3)
% Relative Humidity
0-65535
40029
HL
Low Humidity (External Sensor 3)
% Relative Humidity
0-65535
40038
TC
Current Temperature (External Sensor 1)
Fahrenheit x100
0-65535
40039
TH
High Temperature (External Sensor 1)
Fahrenheit x100
0-65535
40040
TL
Low Temperature (External Sensor 1)
Fahrenheit x100
0-65535
40045
TC
Current Temperature (External Sensor 2)
Fahrenheit x100
0-65535
40046
TH
High Temperature (External Sensor 2)
Fahrenheit x100
0-65535
40047
TL
Low Temperature (External Sensor 2)
Fahrenheit x100
0-65535
40052
TC
Current Temperature (External Sensor 3)
Fahrenheit x100
0-65535
40053
TH
High Temperature (External Sensor 3)
Fahrenheit x100
0-65535
40054
TL
Low Temperature (External Sensor 3)
Fahrenheit x100
0-65535
Table B.1 Read Output Registers (continued)
Register
Name
Description
Units
Range
Table B.2 Family Code (Register 40002, 40009, 40016, 40023: FC)
Hexadecimal 
Value
Decimal Value
Description
0x29
41
8 Switch Sensor
0x10
16
Temperature Sensor
0x26
38
Temperature and Humidity Sensor
0x00
00
No Sensor
Table B.3 Status Flags (Register 40003: SS)
Bit
Status Flag
00
Switch Sensor 1 Status; 1 = On, 0 = Off
01
Switch Sensor 2 Status; 1 = On, 0 = Off
02
Switch Sensor 3 Status; 1 = On, 0 = Off
03
Switch Sensor 4 Status; 1 = On, 0 = Off
04
Switch Sensor 5 Status; 1 = On, 0 = Off
05
Switch Sensor 6 Status; 1 = On, 0 = Off
06
Switch Sensor 7 Status; 1 = On, 0 = Off