American Standard TRACER CH532 Manuel D’Utilisation

Page de 32
LonTalk
®
option
Nv1
0=off
1=on
nv2  range -12.2°C  48.8°C
nv3
0=chiller off
1=chiller on
nv4  range  -40°C  93°C
nv7
1=heat mode
3=cooling mode
nv8  range  10°C  93°C
nv11  range  -40°C  118°C
nv12  range  -40°C  118°C
nv13  range  -40°C  118°C
nv15
manual reset alarm
auto reset alarm
informational warning
circuit 1 fans fault
circuit 2 fans fault
compressor A1 fault
compressor B1 fault
compressor C1 fault
compressor A2 fault
compressor B2 fault
compressor C2 fault
pump 1 fault
pump 2 fault
nv16  chlr_off=0,  chlr_run=2
HVAC_HEAT=1,  HVAC_COOL=3
Chiller state  0=No alarm,  1=In alarm
Run _enable  0=Chiller not allowed to start,  1=Chiller can start
Local  0=Values can be changed remotely,  1=Values cannot be changed remotely
Limited  (Not used)
CHW_flow 0=No water flow,  1=Water flow detected
CONDW_flow  (Not used)
All other bits unused
Configuration properties
nc73
ChillerEnable (m)
nc52
inSendTime (m)
nc4 MaxSendTime 
(m)
nc7 CoolSetpt 
(m)
nc74
Mode (o)
nc78
HeatSetpt (o)
nc48
Heartbeat (o)
(m) = mandatory
(o) = optional
CG-SV01B-E4
27